Double-flap non-return valve DFC.

Body: GGG-50 - flap: steel

Description

Technical data Design Dual plate check valves to be mounted between tow flanges according to EN 1092-1 Type 11 form B – PN10/PN16. Face to face EN 558-1 row 16 Connection DN50 … DN300 Mounting position Pay attention to the flow direction. Preferably mounting into a horizontal runing pipeline. Make sure to install a minimum of 5 x nominal diameter of straight pipeline in front of and behind the dual plate check valve. Do not install the valves directly onto a pump flange. Pressure range PN10 … PN16, see data sheet Temperatur range 0°C … +80°C Media Non aggressive liquids Material Body: GGG-50, FBE-coated Flap: Steel, nickle plated Stem and spring: Stainless steel 1.4301 Seals: EPDM The above information is intended for guidance only and the company reserves the right to change any data herein without prior notice!